Academic Journal of Architecture and Geotechnical Engineering, 2026, 8(1); doi: 10.25236/AJAGE.2026.080118.
Chuan Wang1, Jun Zhang2
1Sichuan Yunkuo Engineering Project Management Co., Ltd., Chengdu, 610045, China
2Shanghai Institute of Technology, Shanghai, 200235, China
Medical buildings in high-seismic-intensity regions must maintain structural safety and essential functions while limiting damage to equipment and nonstructural components. This study examines the application of seismic isolation and energy dissipation technologies in medical public building projects, with emphasis on construction procedures and supervision-based quality control. Drawing on relevant standards, published studies, design and construction documents, and supervision records from representative projects, the study analyzes isolation mechanisms, bearing selection, construction procedures, and quality-control requirements across pre-construction, in-process, and post-construction stages. The analysis identifies five critical control points: incoming bearing inspection, positioning of embedded plates, bearing lifting and installation, protection of completed bearings, and deformation monitoring. Common risks include embedded-plate displacement, damage to bearing protection, blockage of isolation gaps, incomplete monitoring records, and excessive connection gaps. Corresponding measures include dual-person verification, continuous supervision at critical procedures, hierarchical acceptance, standardized documentation, and lifecycle maintenance planning. The findings provide practical guidance for construction supervision and quality management of isolated medical buildings in high-seismic-intensity regions.
Lead-rubber Bearings, Hospital Resilience, Nonstructural Components, Structural Control, Quality Assurance, Construction Supervision, Post-earthquake Functionality
Chuan Wang, Jun Zhang. Seismic Isolation and Energy Dissipation in Medical Buildings: Construction and Quality Control. Academic Journal of Architecture and Geotechnical Engineering (2026), Vol. 8, Issue 1: 145-152. https://doi.org/10.25236/AJAGE.2026.080118.
[1] Soldatova L and Jumukov S. (2006). Seismic isolation of hospital buildings. Smart Structures and Systems, vol.2(4): 329–337. DOI: https://doi.org/10.12989/sss.2006.2.4.329.
[2] Ibrahim O. (2025). Resilience of hospital structures under seismic loads: A case study informed by the 2023 Maras earthquake. Structures, vol.74: 108642. DOI: https://doi.org/10.1016/j.istruc.2025.108642.
[3] Ferraioli M, Avossa AM and Formato F. (2010a). Base isolation seismic retrofit of a hospital building in Italy: Design and construction. COST Action C26: Urban Habitat Constructions under Catastrophic Events: 835–840.
[4] Ferraioli M and Mandara A. (2017). Base isolation for seismic retrofitting of a multiple building structure: Design, construction, and assessment. Mathematical Problems in Engineering: 4645834. DOI: https://doi.org/10.1155/2017/4645834.
[5] Gandelli E, Quaglini V, Dubini P, et al. (2018). Seismic isolation retrofit of hospital buildings with focus on non-structural components. Ingegneria Sismica, vol.35(4): 20–56.
[6] Wen M, Lai X, Qiu WD, et al. (2026). Seismic performance of a partial seismic isolation system for high-rise hospital buildings under near-fault pulse ground motions. Soil Dynamics and Earthquake Engineering, vol.208: 110409. DOI: https://doi.org/10.1016/j.soildyn.2026.110409.
[7] Nikfar F and Konstantinidis D. (2019). Experimental study on the seismic response of equipment on wheels and casters in base-isolated hospitals. Journal of Structural Engineering, vol.145(3): 04019001. DOI: https://doi.org/10.1061/(ASCE)ST.1943-541X.0002266.
[8] Kayıkçı FY and Gürbüz A. (2026). Seismic performance improvement of a reinforced concrete structure with inter-story isolation. Turkish Journal of Civil Engineering, vol.37(2): 47–76. DOI: https://doi.org/10.18400/tjce.1716282.